User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
–
Remote display
parameter block - this parameters lets the user configure the
MultiCon with an external PC to display the screen of MultiCon on the PC monitor,
the parameters of this block are:
•
IP address
- IP address of external PC,
•
Screen number
– can bet set from 0-9 in the MultiCon allowing the PC to
display up to 10 device screens,
–
Server port
– the parameter allowing to set the web server port number where
internet service works. Allows to connect with the device using a web browser on
a selected port. It is also needed while configuring a remote connection with the
device which is outside the local network. It is not recommended to set number ports
which are reserved to standard services.
–
NTP server address
– the parameter which allows to set the NTP server address,
download the curretn time from it and, if necessary, correct the device's system clock
displaying. The device will connect to the NTP server every 15 minutes and correct
its time according to the downloaded server time.
If the
DHCP
parameter is set as
disabled,
the parameters of
IP address
and
Subnet mask
must be configured correctly, depending on the local network settings
which will work with the device. The user should contact the network administrator in
case of errors in communication.
The current network settings are visible in the
Device Information
menu (see
Chapter 7.4.
To establish a connection between the device and PC, port number 6000 must be
unlocked in the software and hardware firewall.
To establish a connection between MultiCon and another device using the TCP/IP
protocol, port number 502 must be unlocked in the software and hardware firewall.
To connect MultiCon with another device using the HTTP protocol, port number 80
must be unlocked in the software and hardware firewall.
255