User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
- Tighten the clamping screws. The recommended tightening torque is 0.5 Nm.
Loose screws can cause fire or defective operation. Over-tightening can lead to
damaging the connections inside the units and breaking the thread.
- In case of the unit fitted with separable clamps they should be inserted into
appropriate connectors in the unit, even if they are not used for any connections.
- Unused terminals (marked as n.c.) must not be used for connecting any
connecting cables (e.g. as bridges), because this can cause damage to the
equipment or electric shock.
- If the unit is equipped with a housing, covers and sealing to protect against water
intrusion, pay special attention to their correct tightening or clamping. In case of
any doubt consider using additional preventive measures (covers, roofing, seals,
etc.). Carelessly executed assembly can increase the risk of electric shock.
- After the installation is completed do not touch the unit’s connections when it is
switched on, because it brings the risk of electric shock.
Due to possible significant interference in industrial installations appropriate measures
assuring correct operation of the unit must be applied. To avoid, the unit of improper
indications, keep recommendations listed below.
Depending on version:
85...
230
...260V AC/DC or
19...
24
...50V DC; 16...
24
...35V AC
Fig. 4.6. Connection of power supply
•
Avoid running signal cables and transmission cables together with power supply cables
and cables controlling inductive loads (e.g. contactors). Such cables should cross each
other at a right angle.
•
Contactor coils and inductive loads should be equipped with interference protection
systems, e.g. RC-type.
•
Use of screened signal cables is recommended. Signal cable screens should be
connected to the earthing only at one of the ends of the screened cable.
•
In case of magnetically induced interference the use of twisted pair signal cables is
recommended. Twisted pair (best if shielded) must be used with RS-485 serial
transmission connections.
•
If measurement or control signals are longer than 30m or go outside of the building, then
additional safety circuits are required.
•
In case of interference from the power supply side, the use of appropriate interference
filters is recommended. Bear in mind that the connection between the filter and the unit
should be as short as possible and the metal housing of the filter must be connected to
the earth with the largest possible surface. The cables connected to the filter output must
not be run together with cables with interference (e.g. circuits controlling relays or
contactors).
15
!
!
FUSE
N
L
N
L
1
2