User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
◦
disabled
- this option turns off screen savers, the LCD screen is illuminated
at all times according to parameter settings:
Backlight
(see the above
Screen saver
parameter block )
◦
1min, 5min, 10min, 30min
,
•
Brightness
- this parameter is hidden for
Mode = disabled
, in the other modes
(
1min
,
5min
,
10min
,
30min
) this parameter is visible, the user can change the
brightness level of the LCD screen after time set in parameter
Mode
elapses.
The options are:
0%
(screen blank),
20%
,
40%
,
60%
,
–
Initial view
parameter block - allows the user to set the initial display screen on the
LCD screen when the device is turned on, this block includes two parameters:
•
Display mode
- select the presentation of data in the displayed group (see
parameter:
Displayed group
). For possible modes see
Chapter 6.3.3. Data
Chapter 7.14. GROUPS
•
Displayed group
- selects a group displayed at startup. If the
Display mode
is
chosen as
many groups
, the parameter
Displayed
group
selects the first of
five following groups displayed on the screen (
many group
mode presents 5
groups in one window). For example, when the user sets
Display group
as
Group 8
then the unit will display: starting from the left side of: Group 8 ->
Group 9 -> Group 10 -> Group 1 -> Group 2,
–
SCADALite
parameter block – this parameter block allows the user to set the home
group for this display mode, this parameter block contains:
•
Home group
– this parameter allows to choice a group, which will be displayed
as a home group after clicking on the button
Home
described in
Chapter 7.1.
–
Automatic view change
parameter block - this parameter block allows the user to
set the display to change every time period. The parameters of this block include:
•
Change mode
- this parameter has the following options:
◦
disabled
- no changes in the display. For this mode the remaining
parameters in this block are not visible,
◦
change modes
- allows the user to automatically change the displayed
mode,
◦
change groups
- allows the user to automatically change a displayed
group,
◦
detailed list
- allows to automatically change displayed views defined by
the user,
•
Triggering mode
– this parameter has the following options:
◦
by time
– it enables to change a displayed view at fixed time intervals,
◦
from log. channel
– changes a displayed view depending on the value in
a selected logical channel. If the value in this channel is less than 1,
the displayed view number is 1, if the value in this parameter equals or is
more than 1 but less than 2 the displayed view number is 2, and so on. The
last defined view does not have the upper limit.
•
Display time
– this parameter is visible for the
Change mode
:
change modes
,
change groups
– duration (set in seconds) for each screen,
•
Triggering source
– this parameter is visible for the
Change mode
:
change modes
,
change groups
, and for the
Triggering mode
:
from log. channel
; it allows the user to choose a logical channel from the list,
whose value will set up the displaying view,
•
Change timeout
– this parameter determines the time from the device startup
or manually change the view to the first automatic view change,
72