User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
recipient (recipients). All recipients must be separated from each other with
a comma or comma and space signs but there can not be more than 78 signs in
total,
•
Subject
– subject of the message,
•
Message text
– additional message text which can be used as a description of
triggering occurrence,
•
Attachment
– parameter which defines what should be attached to the
message. Every message must have an attachment,
◦
disabled
– attachment will not be created and message will not be sent.
When the Attachment parameter is set as disabled all the parameters
described below are not visible,
◦
channels
– attachment will contain Logical channels selected by the user,
◦
groups
– attachment will contain Groups selected by the user,
•
Selected channels
– parameter which is visible only when the
Attachment
parameter is set as channels. Allows to select logical channels from the list
which must be included in the attachment. Until no channel is selected in this
parameter, all the parameters described below will not be visible,
•
Selected groups
– parameter which is visible only when the Attachment
parameter is set as groups. Allows to select groups from the list which must be
included in the attachment. Until no group is selected in this parameter, all
the parameters described below will not be visible,
•
Retry when failed
– parameter which defines if the messages the device was
unable to send will be stored in a queue or not,
◦
yes
– messages will be stored in a queue and sent again,
◦
no
– messages will not be stored and sent again,
•
Expiry period
– this parameter is visible only when the
Retry when failed
parameter is set as yes. Defines for how long (in hours) a message will be
stored in a queue since its first send failure,
•
Triggering channel
– parameter which contains a list of channels where
the selected one will be a triggering source for the message,
•
Trigger mode
– parameter which allows to select the message triggering
method,
◦
rising edge
– switching value in the channel from less or even to zero (≤ 0)
to value greater than zero (> 0) will trigger the message,
◦
falling edge
– switching value in the channel greater than zero (> 0) to
value less or equal zero (≤ 0) will trigger the message.
264