User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
•
Setup list
– this button is visible for
Change mode
parameter setted set as
detailed list
, this parameter is described below in this
Chapter
,
–
PID Autotuning coefficients
parameter block – contains one parameter (
see
Chapter. 7.13. CONTROLLERS
•
Save mode
– it takes two options,
◦
ask before save
– after completing the autotuning process, a window with
information about new PID coefficients appears, after closing it, a standard
configuration save menu appears in which the user can save or reject
settings,
◦
automatic save
– after completing the autotuning process, the
configuration is automatically saved with new PID coefficients,
–
CSV Format settings
parameter block – contains parameters which are related with
creating and sending CSV files,
•
Decimal separator
– selects a decimal separator in the CSV files for numeric
values,
◦
dot
– decimal separator is a dot and a comma will separate all fields in
the CSV files,
◦
comma
– decimal separator is a comma and a semicolon will separate all
fields in the CSV files,
•
List separator
– read only parameter. Changes according to
Decimal
separator
parameter:
◦
comma
– list separator is comma when
Decimal separator
parameter is
set as
dot
,
◦
semicolon
– list separator is semicolon when
Decimal separator
parameter is set as
comma
,
–
Remote shutdown
parameter block – allows to set the automatic shutdown of the
device,
•
Mode
– turns on and off shutdown from a logical channel,
◦
disable
– remote shutdown is off,
◦
from log. channel
– remote shutdown is on,
•
Triggering source
– contains the logical channels list, where the selected one
will be the source for the remote shutdown; the shutdown procedure will start
each time when the signal in the selected channel will change from value
0
to
value
> 0
,
•
Delay
– settable time that will pass before the device will shuts down; this
procedure will be stopped if during this time:
◦
the signal in
Triggering source
parameter will drop to
0
value,
◦
the user will press the
cancel
button on the screen,
When the device starts or when any changes have been made in the
Remote
shutdown
parameter block, and the value in the
Triggering source
parameter in
the selected channel is greater than 0, the shutdown procedure will not start.
To start the shutdown procedure, the value in this channel must change to the
value equal or lower than 0 and then to the value greater than 0.
Setup list
parameter
After pressing the
Setup list
button the user enters the
View
menu allowing the creation of
1
to
20
views.
73