User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
◦
if the
Output list
is empty, press the sign
'+'
to add the output channel
(if the list has defined the output channels, use the arrows in the upper right
corner to select the input channels),
◦
Output active
parameter set as
yes
,
◦
Control type
parameter set as
as a linear output
,
◦
in
Output register
submenu:
–
in
Register number
parameter write
1h
,
–
Data format
parameter set as
32 bits, float
(this depends on
the register format in the Slave device),
–
32-bit reading
parameter set as
two 16-bit registers
,
–
Ordering
parameter set as
CDAB
, because first the younger word part
is sent (Register 1h), then the older part (Register 2h),
◦
press the sign
'+'
and then:
◦
Output active
parameter set as
yes
,
◦
Control type
parameter set as
as a relay
,
◦
in
Output register
submenu:
–
in
Register number
parameter write
4h
,
–
Data format
parameter set as
16 bits, unsigned
(this depends on
the register format in the Slave device),
–
in
Data mask
parameter write
0x0001
,
–
in
Data shift
parameter write
0
,
◦
press the sign
'+'
and then:
◦
Output active
parameter set as
yes
,
◦
Control type
parameter set as
as a relay
,
◦
in
Output register
submenu:
–
in
Register number
parameter write
8h
,
–
Data format
parameter set as
16 bits, unsigned
(this depends on
the register format in the Slave device),
–
in
Data mask
parameter write
0x0001
,
–
in
Data shift
parameter write
0
,
•
Blocks config.mode
parameter set as
manual
,
•
in
Block list
submenu:
◦
Block type
parameters set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to register
format in the Slave device),
◦
in
First register
parameter write
1h
,
◦
in
Last register
parameter write
2h
,
◦
create next block by pressing
'+'
sign,
◦
Block type
parameter set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to register
format in the Slave device),
◦
in
First register
parameter write
4h
,
◦
in
Last register
parameter write
4h
,
◦
create next block by pressing
'+'
sign,
◦
Block type
parameters set as
write HOLDING reg.
,
◦
Register size
parameter set as
16-bit registers
(according to register
format in the Slave device),
◦
in
First register
parameter write
8h
,
◦
in
Last register
parameter write
8h
,
•
move to the
Device templates
parameter block and press
253