AG03/1
Commissioning English
AG03/1 · Date
23.07.2019 · Art.
No.
86426 · Mod.
status
179/19
41
Fig. 11: Address setting
17
DIP switch
17
Address setting Profibus
The DIP switch settings are read in only during switching on voltage sup-
ply. Changing the slave address during operation has no effect.
The slave address is entered via switches 1 - 7 in binary format. The setting
of address 127 is internally set into address 126.
This is illustrated in the following table:
SW1
[2
0
]
SW2
[2
1
]
SW3
[2
2
]
SW4
[2
3
]
SW5
[2
4
]
SW6
[2
5
]
SW7
[2
6
]
set slave
address
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
ON
OFF
OFF
OFF
OFF
OFF
OFF
1
OFF
ON
OFF
OFF
OFF
OFF
OFF
2
ON
ON
OFF
OFF
OFF
OFF
OFF
3
..
..
..
..
..
..
..
..
OFF
OFF
ON
ON
ON
ON
ON
124
ON
OFF
ON
ON
ON
ON
ON
125
OFF
ON
ON
ON
ON
ON
ON
126
ON
ON
ON
ON
ON
ON
ON
126!
Address setting CAN-open
The DIP switch settings are read in only during switching on voltage sup-
ply. Changing the slave address during operation has no effect.
The slave address is entered via switches 1 - 7 in binary format. The setting
of address 127 is internally set into address 126.
NOTICE
NOTICE