Bus-Master
120 R
470 R
+5 V
RS485 -
RS485 +
SGND
DÜA/TxRx +
DÜB/TxRx +
SGND
120 R
470 R
Cable Shield
Node 1 Node n
Fig. 5: Termination and level specificatio RS485 / SIKONETZ5
Permitted power input
Torque overload
The actuator can be irreversibly damaged mechanically in case of abrupt
severe overload (e.g., block travel). Permanent overload causes the actu-
ator to be switched off (e.g., contouring error).
`
Adhere to permitted max. power data as per chapter
.
`
Avoid block travel.
`
Check drive transmission.
`
Check existing torque (adjust acceleration/speed profile, see User
manual).
Sufficiently dimension supply for the actuator. During acceleration, cur-
rent uptake can be temporarily higher than nominal current. The voltage
values depend on the device design. Refer to the technical data in chap-
ter
Operating voltage
•
Wire cross section min. 0,5 mm
2
•
Motor control and output stage are both supplied via the operating
voltage connection.
DANGER
NOTICE