To install the Tilt Mount and Detector:
1
Place the tilt mount in its designated location and secure it with four (4) fasteners
through four (4) holes 7 mm in diameter. Use the 4 screws and spring washers
according to the kit (see Table 15 and Table 16).
Note:
Removing the detector for maintenance purpose does not require the Tilt
Mount to be removed).
2
Unpack the detector.
3
Place the detector with its conduit/cable entries pointing downwards on the holding
plate of the tilt mount. Secure the detector with
5
/
16
" 18 UNC x 1" screw to the tilt
mount.
4
Release the Horizontal and Vertical Locking Screws using
3
/
16
" Hex Key such that
the detector can be rotated. Point the detector towards the protected area and
make certain that the view of the area is unobstructed. Secure the detector in that
position by tightening the locking screws on the tilt mount. (Make sure the detector
is in the correct position.).
The detector is now correctly located, aligned and ready to be connected to the
system.
2.7
CONNECTING THE DETECTOR
This section describes how to connect the electric cabling to the detector (Figure 7).
➣
To connect the detector to the electrical cables
1
Disconnect the power.
2
Remove the back cover of the detector by removing four (4) socket head-screws in
the cover bolts. The terminal chamber is now revealed.
3
Remove the protective plug mounted on the Detector Conduit/Cable entry; pull the
wires through the Detector Inlet.
4
Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5 flameproof
gland to assemble the cable / conduit to the detector.