Table 5: Welding Immunity Distance
Sensitivity Setting
Detection Range
Immunity Distance
1
50 ft (15m)
>6 ft (2m)
2
100 ft (30m)
>12 ft (4m)
3
150 ft (45m)
>17 ft (6m)
4
215 ft (65m)
>25 ft (7.5m)
1.5.4 VISUAL
INDICATORS
One 3-color LED indicator is located inside the detector window, as shown in Figure 3.
The detector statuses are listed in Table 6.
Table 6: LED Indications
Detector Status
LED color
LED mode
Fault, BIT Fault
Yellow
4 Hz - flashing
Normal
Green
1 Hz - flashing
Warning
Red
2 Hz - flashing
Alarm Red Steady
Figure 3: Indicator LED
Indicator LED