3600I
Page: 38
A SPECIFICATIONS
➣
In this appendix…
Technical Specifications
page 38
Electrical Specifications
page 39
Outputs page
39
Mechanical Specifications
page 41
Dimensions page
41
Weight page
41
Environmental Specifications
page 42
A.1 TECHNICAL
SPECIFICATIONS
Spectral Response
Three IR Bands
Detection Range
(at highest Sensitivity Setting for
1ft
2
(0.1m
2
) pan fire)
Fuel
ft / m
Fuel
ft / m
n-Heptane
215 / 65
Kerosene
150 / 45
Gasoline
215 / 65
Ethanol 95%
135 / 40
Diesel Fuel
150 / 45
Methanol
115 / 35
JP5
150 / 45
IPA (Isopropyl
Alcohol)
135 / 40
Methane*
100 / 30
Polypropylene
Pellets
16 / 5
LPG*
100 / 30
Office Paper
33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
4 Sensitive ranges for 1 ft
2
(0.1m
2
) n-heptane pan fire from
50 ft (15m) to 215 ft (65m)
Fields of View
Horizontal 100
°
, Vertical 95
°
Built-In-Test (BIT)
Automatic (and Manual)
Содержание 3600I