D.1.3 RANGE
Table 30: Sensitivity Ranges
Sensitivity
Detection Range
(ft / m)
Standard Test
Range (ft / m)
Extended Test
Range (ft / m)
1 (Low)
50 / 15
3.8 / 1.2
7 / 2.2
2
100 / 30
7 /2.2
14.5 / 4.5
3
150 / 45
10 / 3.2
22 / 7
4 (High)
215 / 65
14.5 / 4.5
29 / 9
Notes
:
•
The minimum distance from the detector is 20 inches (50 cm).
•
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the range.
Important
: Keep the Fire Simulator in a safe place when not in use.
D.1.4
CHARGING THE BATTERY
The Fire Simulator uses NiCd batteries as a rechargeable power source. When the
batteries are fully charged, the simulator operates for at least 60 times without
recharging. An internal buzzer is sounded when the voltage from the batteries is lower
than the required operational level.
➣
To charge the battery:
1
Place the Fire Simulator on a table in a safe area.
2
Turn the sealed plug (next to the operation button) counter-clockwise with a suitable
wrench.
3
Connect the battery charger.
4
Charge for a maximum of 14 hours.
5
Disconnect the charger.
6
Tighten the sealed plug clockwise.