3600I
Page: 26
Table 17: Model 3600I Wiring Options
Wire
Terminal No.
Option 1
Default
Option 2
Option 3
Option 4
Option 5
1
+24 VDC
+24 VDC
+24 VDC
+24 VDC
+24 VDC
2
0 VDC
0 VDC
0 VDC
0 VDC
0 VDC
3
Manual BIT
Manual BIT
Manual BIT
Manual BIT
Manual BIT
4
Fault Relay
N.C.
Fault Relay
N.C.
Fault Relay
N.O.
Fault Relay
N.C.
Fault Relay
N.O.
5
6 Alarm
Relay
N.O.
Alarm Relay
N.O.
Alarm Relay
N.O.
Alarm Relay
N.O.
Alarm Relay
N.O.
7
Alarm Relay C
Alarm Relay
C
Alarm Relay
C
Alarm Relay
C
Alarm Relay
C
8 0-20mA
In
Alarm Relay
N.C.
Alarm Relay
N.C.
Auxiliary
N.O.
Auxiliary
N.O.
9
0-20mA Out
0-20mA
Out*
0-20mA
Out*
Auxiliary
C
Auxiliary C
10 RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
RS-485+
(1)
11 RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
RS-485-
(1)
12 RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
RS-485
GND
* Available with the HART protocol.
Notes
:
•
RS-485 is used for communication network as specified in
Appendix C
(Terminals
10, 11, 12) and to connect (in safe area) to PC/Laptop for configuration/diagnostics.
•
Alarm
relay:
•
N.O. energized contact in wiring options 1, 4, 5.
•
N.O. and N.C. energized in options 2 and 3.
•
0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.
•
0-20mA ‘Source’ in options 2 and 3 available with the HART protocol.
•
In Wiring Option 1, link Terminals 1 and 8 to change the mA output to ‘Source’.
•
The Fault output is N.C. energized SPST relay. The contacts are closed when the
Detector is in its normal operational condition in options 1, 2 and 4, and available as
N.O. energized in options 3 and 5.
•
The Auxiliary output is N.O. energized (SPST) relay. The Auxiliary Relay may act in
parallel with the ALARM relay to activate another external device or it may provide a
warning signal, depending on the function configuration.