3600I
Page: 50
•
Fire Simulator with integral batteries
•
Battery
charger
•
Optional Beam Collimator
•
Storage
case
D.1.2 OPERATING
INSTRUCTIONS
Warning
: Do not open the Fire Simulator to charge the batteries or for any other reason
in a hazardous area.
Caution
: The following test simulates a real fire condition and may activate the
extinguishing system or other alarms. If this is not desired, disconnect/inhibit them
before the test and reconnect after the simulation.
➣
To simulate a fire:
1
Aim the Fire Simulator towards the detector’s Target Point.
Figure 16: 3600I IR3 Detector Target Point
2
When testing keep a distance of at least 50 cm (20 inches) from the detector.
3
Press the operation button once. Fire simulation lasts for 20 seconds. The detector
sends an alarm signal (solid red LED).
4
Wait 20 seconds before repeating the test.
5
Verify that the optical window is clean.
Target Point
Содержание 3600I
Страница 17: ...3600I Page 9 Vertical 50 down 45 up Figure 2 Vertical Field of View...