3600I
Page: 39
A.2 ELECTRICAL
SPECIFICATIONS
Table 23: Electrical Specifications
Operating Voltage
Status
All
Outputs
Without 0-
20mA
Power Consumption
(Max. 24VDC)
Normal 1.61W
1.56W
Normal when Heater On
2.28W
2.16W
Alarm
2.64W
2.28W
Alarm when Heater On
3.24W
2.88W
Maximum Current
(Max. 24VDC)
Normal 70mA
65mA
Normal when Heater On
95mA
90mA
Alarm 110mA
95mA
Alarm when Heater On
135mA
120mA
Power Consumption
(Max. 18-32VDC)
Normal 1.95W
1.85W
Normal when Heater On
2.56W
2.45W
Alarm 3.04W
2.56W
Alarm when Heater On
3.68W
3.2W
Maximum Current
(18-32VDC)
Normal 90mA
85mA
Normal when Heater On
105mA
100mA
Alarm 130mA
115mA
Alarm when Heater On
160mA
145mA
Electrical Input Protection
The input circuit is protected against voltage-
reversed polarity, voltage transients, surges and
spikes according to MIL-STD-1275B
A.3 OUTPUTS
Electrical
Interface
There are five output-wiring options. These options must be
defined at the factory per the customer order and cannot be
changed at the customer facility.
See
General Instructions for Electrical Wiring
on page 43 for the
wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The wiring
arrangement is identified on the detector by the part number (see
Model and Types
on page 2).
•
Option 1
: Power, RS-485, 0-20mA (Sink), Fault I Relay (N.C),
Alarm Relay, (N.O) (see Figure 7).
•
Option 2
: Power, RS-485, 0-20mA (Source) and HART
protocol, Fault Relay (N.O), Alarm Relay, (N.O), (N.C).
•
Option 3
: Power, RS-485, 0-20mA (Source) and HART
Protocol, Fault Relay (N.O), Alarm Relay (N.O, N.C).