CONFIGURING YOUR DETECTOR
You can reprogram the function setup using the RS-485 connection or using the Hart
Protocol as follows:
•
Sierra Monitor Host Software
: The Sierra Monitor Host Software is for use on a
PC or laptop. Refer to Manual TM777050 for programming instructions. The Host
software enables you to change the functions.
•
Handheld Unit
: Refer to Manual 777060 for programming instructions when using
the Handheld Unit. The connection to the Handheld is fast and intrinsically safe. It
enables you to change the functions in situ with no need to remove the detector.
Note
: Sierra Monitor can provide a suitable cable (P/N 794079-5) with integral
RS485/USB converter to connect between the Detector and a PC/laptop.
•
Hart Protocol
: Refer to Manual TM 777030 for programming instructions.
These functions enable you to set:
•
Sensitivity
•
Alarm
Delay
•
Time Delay for Anti Flare mode
•
Address
Setup
•
Mode of Operation
•
Heated Optics Operation
The factory Default settings listed for each function are:
•
Sensitivity
–
30
•
Alarm Delay – A
•
Alarm Latch – No
•
Auxiliary Relay – No
•
Automatic BIT – Yes
•
Alarm BIT – No
•
Auxiliary BIT – No
•
EOL – No
•
Heated Optics – Auto
•
Temperature – 41°F (5°C)