Output
Effect of load impedance
< 0.025% of max. span / 100 Ω
Long-term drift
< 0.025% of max. span in the first month
< 0.035% of max. span after one year
< 0.05% of the max. span after 5 years
Note
Measurement errors
Greater measuring errors may occur if the transmitter is installed on a DIN rail in an environment
with severe interference. Observe the applicable ESD directives.
Operating conditions
Ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
Relative humidity
≤ 98%, condensing
Electromagnetic compatibility
As per EN 61326 and NAMUR NE21
Errors with EMC influences
• ESD in accordance with
EN 61000-4-2
< 0.10% of measuring span
• HF radiation according to
EN 61000-4-3
< 0.8% of measuring range 0 ... 100 °C
• Burst in accordance with
EN 61000-4-4
< 0.1% of measuring range 0 ... 100 °C
• HF energizing according to
EN 61000-4-6
< 0.9% of measuring range 0 ... 100 °C
Table 12-1
Mechanical construction
Core cross-section
Max. 2.5 mm
2
(AWG 13)
Weight
50 g
Dimensions
See SITRANS TH100 dimension drawings (Page 217)
Material
Molded plastic
Degree of protection
In accordance with IEC 60529
• Housing
IP40
• Terminals
IP00
Factory setting Pt100 (DIN IEC)
In three-wire input
Measuring range
0 ... +100 °C (32 ... +212 °F)
Fault current
22.8 mA
Technical data
12.1 SITRANS TH100
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
194
Operating Instructions, 05/2020, A5E41864807-AB