Display
– NAMUR NE 107
NAMUR
– HCF
SIMATIC PDM/PLC
Symbol
Device status
Priority *
Symbol
Device status
Priority *
Function test
2
(yellow)
Configuration warning
9
Cause: Safety validation is not complete.
Measure: Acknowledge safety event in the Functional Safety menu and repeat safety commissioning.
Out of specifica‐
tion
3
Process value warning
10
Cause: Deviations from permissible ambient or process conditions detected by the device (by means of self-monitoring or
based on warnings/errors in the device) indicate that the measured value is unreliable or that deviations from the set value in
the actuators are most likely greater than anticipated under normal operating conditions.
Process or ambient conditions can damage the device or result in unreliable results.
Measure: Check ambient temperature or process conditions. If possible, install device at different location.
No symbol is
displayed
Process value tolerance
11
Cause: At least one process value violates one of the process tolerance limits set in the device parameters.
Measure: Check the parameter settings for limits for this application.
No symbol is
displayed
No symbol is
displayed
Configuration changed
12
Cause:The device configuration has changed due to a work process.
Measure: Reset configuration bit memory to delete the diagnostic message.
No symbol is
displayed
Good – OK
No symbol is
displayed
No assignment
13
Cause: Device state ok. No errors from active diagnostics.
Measure: No action required.
* The smallest number indicates the highest level of error severity.
** In SIMATIC PDM, the Siemens standard symbol as well as the corresponding NA\ symbol is
displayed (by the device display).
Diagnostics and troubleshooting
11.1 Device status symbols
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
187