3. Press the button.
4. Set the damping with the and buttons.
5. To set the damping in steps of 0.10 s, press and hold down the buttons.
6. Use the
button to confirm.
9.3.11
Functional Safety [12]
Enables Functional Safety.
The parameter is only visible for devices with Functional Safety.
See also
Functional Safety Manual (
https://www.siemens.com/processinstrumentation/documentation
)
9.3.12
Loop test [13]
Sets a constant loop current for test purposes.
You have the option of selecting preset values or a user-defined value.
Setting range:
3.55 mA
4 mA
12 mA
20 mA
22.8 mA
USER
User defined
Factory setting:
12 mA
9.3.12.1
Loop test with preset loop current value
1. Navigate into the parameter view.
Navigating in the views (Page 107)
2. Select the parameter "Loop test".
Parameter assignment
9.3 Parameter assignment over device with display
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
150
Operating Instructions, 05/2020, A5E41864807-AB