WARNING
Unsuitable cables, cable glands and/or plugs
Risk of explosion in hazardous areas.
• Use only cable glands/plugs that comply with the requirements for the relevant type of
protection.
• Tighten the cable glands in accordance with the torques specified in Technical data
(Page 193).
• Close unused cable inlets for the electrical connections.
• When replacing cable glands, only use cable glands of the same type.
• After installation, check that the cables are seated firmly.
WARNING
Improper power supply
Risk of explosion in hazardous areas as result of incorrect power supply.
• Connect the device in accordance with the specified power supply and signal circuits. The
relevant specifications can be found in the certificates, in Technical data (Page 193) or on
the nameplate.
NOTICE
Ambient temperature too high
Damage to cable sheath.
• At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an
ambient temperature at least 20 °C (36 °F) higher.
WARNING
Connecting device in energized state
Risk of explosion in hazardous areas.
• Connect devices in hazardous areas only in a de-energized state.
Exceptions:
• Devices having the type of protection "Intrinsic safety Ex i" may also be connected in
energized state in hazardous areas.
• Exceptions for type of protection "Non-sparking nA/ec" (Zone 2) are regulated in the
relevant certificate.
Connecting
6.1 Basic safety notes