SITRANS LR200 with mA/HART
50
Operating Instructions, 05/2019, A5E32337676-AE
①
Sensor reference point
⑥
A=0.8 m
②
0.5 m
⑦
L=6 m
③
High calibration point
⑧
Volume reading
④
3.5 m
⑨
100%=8000 L
⑤
Low calibration point
Parameter
type
Parameter no./name
Options/values
Function
Quick Start
Wizard pa-
rameters
Material (1.2.)
LIQUID
Response Rate (1.3.)
MED
Medium =1 m/minute
Units (1.4.)
M
meters
Operating Mode (1.5.)
LEVEL
Level is reported as
Volume when a vessel
shape is selected.
Low Calibration Point (1.6.)
3.5
3.5 m (11.48 ft)
High Calibration Point (1.7.)
0.5
0.5 m (1.64 ft)
Apply? (Apply changes) (1.8.)
YES
Transfers Quick Start
settings to device.
Independent
parameters
(Page 107)
PARABOLIC ENDS
Defines vessel shape
(Page 108)
8000
8000 liters
(Page 108)
0.8
0.8 m (2.62 ft)
(Page 109)
6
6 m (19.68 ft)
Timer (2.5.2.) (Page 103)
2
2 minutes
(Page 103)
HI
Fail-safe level set to
High
Range (2.8.7.2.) (Page 117)
[Distance
1
minus 0.42
m]
Sets length of learned
TVT curve
2
to use
(2.8.7.1.) (Page 115)
LEARN
Enables the use of
learned TVT curve
2
1)
Distance to product from sensor reference point.
2)
For more details, refer to Auto false echo suppression (2.8.7.1.) (Page 115) and Auto false
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...