SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
133
7.4.11
Memory test (4.11)
Description
Allows verification of the RAM, EEPROM, and flash memory of the device
LCD display
IDLE
No test in progress
BUSY
Test in progress
PASS
Memory test successful
FAIL
Test failed
Err1
Test returned unexpected results
P Oxcafe
Test passed with result data
F Oxcafe
Test failed with result data
Handheld pro-
grammer entry
to
Any numeric key from 1 to 9 activates
test
1.
Press RIGHT arrow
to edit then press any numeric key from 1 to 9 to activate the
test.
2.
The reading will display BUS and then the test result text.
7.5
Communication (5.)
7.5.1
Device address (5.1.)
Description
Sets the device address or poll ID on a HART network. Any address other than 0
will cause the output current to be a fixed value, and the current will not indicate
the reading.
Values
Range: 0 to 15
Factory setting
0
To reset Device Address via SIMATIC PDM:
1.
Open the project in Process Device Network View then right click on the device.
2.
Go to Object Properties > Connection to access the field Short Address.
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...