SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
143
Code/
Icon
Meaning
Corrective Action
S: 37
*
Measurement hardware problem.
Replacement required: contact your local Siemens repre-
sentative
S: 38
*
Failure in the device electronics.
Replacement required: contact your local Siemens repre-
sentative
S: 43
*
Factory calibration for the radar receiver has
been lost.
Replacement required: contact your local Siemens repre-
sentative.
S: 45
*
No valid boot program detected: firmware cor-
rupt
Replacement required: contact your local Siemens repre-
sentative.
S: 48
*
User configuration is invalid. One or more of
parameters: Low Calibration Point, High Cali-
bration Point, Volume breakpoints, and/or Auto
False-Echo Suppression, are set to invalid
values.
•
Reconfigure the unit.
•
Ensure the difference between High Calibration Point
and Low Calibration Point is not less than or equal to
zero; do a Master Reset.
S: 49
*
EEPROM corrupt.
Replacement required: contact your local Siemens repre-
sentative.
S: 50
*
EEPROM corrupt.
Replacement required: contact your local Siemens repre-
sentative.
S: 51
*
EEPROM corrupt.
Replacement required: contact your local Siemens repre-
sentative.
S: 52
Fail-safe is activated. Possible causes:
1.
hardware failure
2.
memory failure
3.
Fail-safe LOE timer expired– possible
causes: faulty installation, antenna material
buildup, foaming/other adverse process
conditions, invalid calibration range.
For 3:
•
Correct configuration; ensure installation is correct;
•
no antenna buildup;
•
adjust process conditions to minimize foaming/other
adverse conditions;
•
correct calibration range.
If fault persists, or for 1 and 2, contact your local Siemens
representative.
S: 53
*
Configuration lost: one or more parameter
settings have been lost. This may occur after a
firmware upgrade causes user parameters to
be reset.
Restore user parameters using SIMATIC PDM.
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...