![Siemens SITRANS LR200 7ML5422 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/siemens/sitrans-lr200-7ml5422/sitrans-lr200-7ml5422_operating-instructions-manual_384663031.webp)
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
31
①
Use a 2 mm Allen key loosen the lid-lock
set screw.
④
Locking ring
②
Plug
⑤
Threaded connection
③
Optional cable gland
1) 2)
(or NPT cable entry
2)
)
If you want to rotate the enclosure, use the 2 mm Allen key to loosen the locking ring.
1.
Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and
thread the wires through the gland
2)
.
2.
Connect the wires to the terminals as shown: the polarity is identified on the terminal
block.
3.
Ground the instrument according to local regulations.
4.
Tighten the gland to form a good seal.
5.
Close the lid and secure the locking ring before programming and device configuration