SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
53
①
Sensor reference point
⑤
Low calibration point
②
0.5 m
⑥
5 m
③
Vent hole
⑦
High calibration point
④
50 mm I.D.
Parameter
type
Parameter no./name
Options/Values Function
Quick start
wizard
Material (1.2.)
LIQUID LOW
DK
Response Rate (1.3.)
MED
Medium =1 m/minute
Units (1.4.)
M
meters
Operating Mode (1.5.)
LEVEL
Level is reported as Volume when a
vessel shape is selected.
Low Calibration Point (1.6.) 5
5 m (16.5 ft)
High Calibration Point (1.7.) 0.5
0.5 m (1.64 ft)
Apply? (Apply changes)
(1.8.)
YES
Transfers Quick Start settings to
device.
Independent
parameters
(Page 111)
1)
0.990
P.F. for a 50 mm (1.96") I.D. stillpipe
(Page 112)
HYBRID
(Page 112)
1)
4.3
4.3 m (14.10 ft)
1)
The recommended values for the propagation factor and for CLEF range are dependent on the
stillpipe diameter. Refer to the next table for values.
6.2.2.5
Propagation factor/Stillpipe diameter
Nominal Pipe
Size
1)
40 mm (1.5”)
50 mm (2”)
80 mm (3”)
100 mm (4”)
Propagation Fac-
tor
0.9828
0.990
0.991
0.9965
CLEF Range
(2.8.4.4.) settings
Low Cal Pt. – 700
mm
Low Cal Pt. – 700
mm
Low Cal Pt. –
1000 mm
Low Cal Pt. –
1000 mm
1)
Since pipe dimensions may vary slightly, the propagation factor may also vary.
Содержание SITRANS LR200 7ML5422
Страница 185: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 185 B 5 4 PFTE rod antenna threaded connection ...
Страница 193: ...SITRANS LR200 with mA HART Operating Instructions 05 2019 A5E32337676 AE 193 ...
Страница 194: ...SITRANS LR200 with mA HART 194 Operating Instructions 05 2019 A5E32337676 AE ...
Страница 212: ...Index SITRANS LR200 with mA HART 212 Operating Instructions 05 2019 A5E32337676 AE ...