SITRANS LR200 with mA/HART
116
Operating Instructions, 05/2019, A5E32337676-AE
After Auto False Echo Suppression
①
Learned TVT
②
Default TVT
③
Material level
④
Echo marker
⑤
Auto False Echo Suppression Range
⑥
False echo
To set Auto False Echo Suppression via SIMATIC PDM:
Open the menu Device – Echo Profile Utilities and click on the tab Auto False Echo
Suppression. For more detailed instructions, refer to Auto false echo suppression (Page 67).
To set Auto False Echo Suppression via the handheld programmer:
Options
OFF
Default TVT will be used
ON (factory setting)
'Learned' TVT will be used
LEARN
'Learn' the TVT
3. Go to Auto false echo suppression range (2.8.7.2.) (Page 117) and enter the value
calculated in step 2.
4. Go to Auto false echo suppression (2.8.7.1.) (Page 115) and press RIGHT arrow to open
Edit Mode.
5. Select Learn. The device will automatically revert to On (use "Learned TVT") after a few
seconds.