Operation
8.5 Special functions
Installation and Operating Instructions SINAMICS G180
158
Operating Instructions, 02/2019, 4BS0751-007
Table 8- 8
Line contactor functions
Terminal / compo-
nent
Function
-F1
External control voltage fuse protection
-F2
Inverter output section fuse protection
-K1
Input side main contactor
Design recommendation: AC1 current of the contactor is at least the inverter input current
101, 102
External control voltage for the 230 V inverter
41, 42
Digital output for the main contactor control
U1, V1, W1
Mains power connection switched via main contactor
8
Main contactor feedback input
55
24 V DC supply voltage
1, 51
Jumper for ground connection
U2, V2, W2
Motor connection
NOTICE
Coil currents in excess of 1 A at contact 41/42
If you load the contact 41/42 with coil currents of more than 1 A, the contact can be
destroyed.
In the case of coil currents of more than 1 A, connect an auxiliary relay between terminal
41/42 and the main contactor coil.
Make the following settings in order to activate the main contactor function:
●
The preselection for the inputs/outputs for the control must be as follows:
–
"P-DRIVE DATA/A=Namur" or
–
"P-DIGITAL OUTPUTS/Relay 2=MainCntctr" and "P-OPERATION/Feedb.MC=X2:8"
●
For "P-INV. BEHAVIOUR/MCfunc" the setting "LinC…" must be input.