Electrical connection
6.7 External control voltage
Installation and Operating Instructions SINAMICS G180
112
Operating Instructions, 02/2019, 4BS0751-007
6.7.3
Connecting the external 24 V DC control voltage
6.7.3.1
Protecting/fusing the external 24 V DC control voltage
NOTICE
External control voltage without fuse protection
If you use an external control voltage without suitable protection (e.g. fuses), then
overloads and short-circuits can occur. Material damage can result.
The device may only be operated with a protected external control voltage. Note the
following recommendation.
Install one of the following options to protect the external control voltage:
●
Miniature fuse in accordance with EN 60127: 6 A, slow acting, maximum 100 VA
●
Miniature circuit-breaker: 6 A, characteristic D, maximum 100 VA
6.7.3.2
Switching over the hardware to an external 24 V DC control voltage
●
Change the converter from internal control voltage via the DC link to external control
voltage.
●
Replace the PC board switch mode power supply L0353151 by PC board SNT24V
L0353161.
Procedure
Connect the external control voltage to the terminals 1 (0 V) and 2 (+24 V).