Commissioning
7.2 Checks with mains power supply and without motor
Installation and Operating Instructions SINAMICS G180
118
Operating Instructions, 02/2019, 4BS0751-007
Selecting application and mode
●
It is not necessary to select an application for converters which have been fitted with a
signal controller at the factory.
●
The parameter assignment is adapted in the factory when the unit is being tested and is
stored under the menu "P-DRIVE DATA/A" in the "Factory_Settings" application.
●
Select the desired application under "P-DRIVE DATA/A", and select the desired operation
under "P-OPERATION/Opr.".
–
Use the associated wiring diagram in the Appendix for this. The "Standard" application
is set as the default at the factory.
–
For additional information, refer to the section titled "Standard" application"
(Page 168).
●
If you would like to make other changes to the parameters, these changes can be made
at this point.
In this case, the parameter "P-DRIVE DATA/A=Standard" changes to "P-DRIVE
DATA/A=specific".
Note
Loss of all configured values
If you select other applications before the changed parameters have been saved, all
values already set will be lost. Save the changed parameters before selecting other
applications.
Checking mains power supply parameters
1.
Set your mains rated voltage in the menu item "P-INVERTER DATA/V mains nom.".
If necessary, set the controller / fan transformer correctly.
2.
For additional information, refer to the section titled "Mains connection" (Page 93).
Adapting motor data
1.
Under "P-MOTOR DATA"/ first set the controller variant of the converter or the motor
type.
Содержание SINAMICS G180