Electrical connection
6.6 Motor connection
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
99
6.6.2
Coil load
Note
Voltage increases due to switching flanks
The switching flanks in the voltage produced by the inverter also load the motor insulation.
Excess voltages occur.
If you observe the instructions in this section, voltage peaks at the motor of more than 1,560
V do not occur. Motors which are dimensioned for inverter operation therefore do not cause
any problems. If you would like to connect older motors or motors which are not suitable for
inverter operation, please consult the motor manufacturer.
Pay attention to the exact compliance with the peak voltage in the motor for explosion-
protected motors.
6.6.3
Motor voltage and type of circuit
Operate the motor as "star" or "delta" type of circuit according to the parameterization of the
inverter.
In most cases, the parameterized motor voltage on the inverter is identical to the mains
voltage. Check the parameter "P-MOTOR DATA/V-motor".