Electrical connection
6.6 Motor connection
Installation and Operating Instructions SINAMICS G180
98
Operating Instructions, 02/2019, 4BS0751-007
①
Jumpers for rated voltage preselection
②
Terminals -X101 and -X102 for an external control voltage
③
Terminal for preselection of the control voltage setting
•
View as in the picture: Internal power supply
•
Cable connected at connector -X200 : Power supply via terminals -X101 and -X102
Figure 6-1
Jumpers and terminals on the inverter
If a transformer is installed in a cabinet unit, the transformer connections must be changed to
the correct line voltage.
6.6
Motor connection
6.6.1
Motor selection
Three-phase asynchronous motors or three-phase synchronous motors can be used for your
inverter. The use of several motors simultaneously is permitted.
●
The total of the motor outputs must not exceed the inverter output. You may operate
smaller and larger motors in parallel on one inverter.
●
Take into account during the motor dimensioning that additional losses in the motor are
produced by the non-sine shaped motor current.
●
Note that a motor without external ventilation will be cooled less at speeds less than the
rated speed. Therefore, consult the motor manufacturer for the dimensioning of the
motor.
●
When using Siemens motors, refer to the list "UN03/UN04 Drehstrommotoren für
drehzahlverstellbare Antriebe" to find the relevant inverter output.
Содержание SINAMICS G180
Страница 1: ......
Страница 2: ......
Страница 194: ...Quality documents Installation and Operating Instructions SINAMICS G180 192 Operating Instructions 02 2019 4BS0751 007 ...
Страница 217: ......
Страница 218: ......