Description
3.3 Accessories
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
53
Figure 3-4
DC network
Please observe the following:
●
Inverter 1 and Inverter 2 must be the same type.
●
Connect both inverters to the mains power using a common supply line.
●
Operate the mains power feed-in current of each inverter at maximum 75% of the rated
current.
●
The mains power supply connection cables from –K1:2, 4, 6 to both inverters must be the
same length and have the same cross-section.
●
You can use a normal cable to connect the DC link, e.g. H07VK in the cabinet, or NYY
outside the cabinet.