
Commissioning
4.2 Restoring the factory settings
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
47
4.2
Restoring the factory settings
If nothing else works, restore the factory settings!
You can restore the factory settings using parameter P0970.
Parameter or
procedure
Description
P0003 = 1
User access level
1: Standard level
P0010 = 30
Commissioning parameter
30: Factory setting, parameter transfer
P0970 = 1
Restore factory settings
1: Restore the factory parameter settings
BOP displays "BUSY"
STARTER displays
progress bar
Once the factory settings have been restored, P0970 and P0010 are set to 0
and the BOP returns to the standard display.
Note
Data transfer is interrupted while the factory parameter settings are being restored.
The following parameters remain unchanged even after the factory settings have been
restored:
•
P0014 Storage mode
•
P0100 Europe / North America
•
P0201 Power stack code number
•
Communication parameters
•
Power-Module-specific data