5.9 Evaluating the frequency inverter status
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
125
Table 5- 33 Changing the digital output settings
Terminal No., significance
Parameter Description
P0003 = 2
Extended parameter access
18
NC
19
NO
20
COM
Digital output 0
P0731
21
NO
22
COM
Digital output 1
P0732
23
NC
24
NO
25
COM
Digital output 2
P0733
Possible values for P0731, P0732 and P0732:
0 Deactivate digital output
52.0 Drive ready
52.1 Drive ready for operation
52.2 Drive running
52.3 Drive fault active
52.4 OFF2 active
52.5 OFF3 active
52.6 Switching on inhibited
52.7 Drive alarm active
52.8 Setpoint/actual value deviation
52.9 PZD control
52.10 f_act >= P1082 (f_max)
52.11 Alarm: Motor current/torque limiting
52.12 Brake active
52.13 Motor overload
52.14 Motor CW rotation
52.15 Inverter overload
53.0 DC brake active
53.1 f_act < P2167 (f_off)
53.2f_act > P1080 (f_min)
53.3 Current actual value r0027 ≥ P2170
53.6 f_act ≥ setpoint (f_set)
P0748
Invert digital outputs
Bit 0: Digital output 0
Bit 1: Digital output 1
Bit 2: Digital output 2
Further, the digital outputs can be interconnected with all binector outputs. A list of the
binector outputs is provided in the List Manual.