Functions
5.9 Evaluating the frequency inverter status
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
127
Table 5- 36 Additional analog output settings
Parameter
Description
P0775 = 0
Permit absolute value
Specifies whether or not the absolute value of the analog output is used.
If enabled, this parameter will use the absolute value of the value to be output. If the
original value was negative, the corresponding bit is set in r0785.
P0776 = 0
Analog output type
Scaling of r0774.
0: Current output (factory setting)
1: Voltage output
Note: P0776 changes the scaling of r0774 (0 to 20 mA ⇔ 0 to 10 V).
The scaling parameters P0778 and P0780 as well as the dead band are always
entered with 0 to 20 mA.
Analog output 0 can be switched as a voltage output between 0 and 10 V.
Analog output 1 is a current output only. If it is to be used as a voltage output, it must
be terminated with a 500 Ω resistor.
P0777 = 0.0
Value x1 for analog output scaling
Defines output characteristic x1 (in %). This parameter is the minimum analog value
expressed as a percentage of P200x (depending on how P0771 is set).
P0778 = 0
Value y1 for analog output scaling
This parameter is the value of x1 (in mA).
P0779 = 100 Value x2 for analog output scaling
This defines x2 of the output characteristic as a
percentage. This parameter is the maximum
analog value expressed as a percentage of P200x
(depending on how P0771 is set).
P0780 = 20
Value y2 for analog output scaling
This parameter is the value of x2 (in mA).
P0781 = 0
Dead band width of the analog output
This can be used to set the width of the dead
band for the analog output (in mA).