Functions
5.10 Technological functions
Frequency inverter
148
Operating Instructions, 08.10. 2008, t.b.d.
Table 5- 47 Parameters for switching the drive data sets:
Parameter
Description
P0820 = …
1st cntrol command for switching the drive data sets
Example: When P0820 = 722.0, the system switches from drive data set 0 to drive
data set 1 via digital input 0
P0821 = …
2nd control command for switching the drive data sets
r0051
Displaying the number of the DDS that is currently active
A copy function is available making it easier to commission more than one drive data set:
P0819.0 = … Number of the drive data set to be copied (source)
P0819.1 = … Number of the drive data to which the data is to be copied (target)
P0819.2 = 1 Start copying
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the List Manual.