Technical data
8.3 Common technical data, PM240 Power Modules
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
225
8.3
Common technical data, PM240 Power Modules
PM240
Feature
Version
Line operating voltage
3 AC 380 V … 480 V ± 10%
The permissible line operating voltage
depends on the installation altitude
Input frequency
47 Hz … 63 Hz
Power factor λ
0.7 ... 0.85
The Power Module PM240 can either be operated with high overload
(HO) or low overload (LO). In order to avoid overtemperature of the
Power Module, after the overload, as a minimum its load must decrease
back to the base load (HO base load or LO base load).
HO base load
0.37 kW ... 75 kW
150% overload for 57 s
200% overload for 3 s
100% HO base load for 240 s
HO base load
90 kW ... 200 kW
136% overload for 57 s
160% overload for 3 s
100% HO base load for 240 s
LO base load
7.5 kW ... 90 kW
110% overload for 57 s
150% overload for 3 s
100% LO base load for 240 s
Overload capability
LO base load
110 kW ... 250 kW
110% overload for 59 s
150% overload for 1 s
100% LO base load for 240 s
Pulse frequency
4 kHz for 0.37 kW ... 75 kW (HO)
2 kHz for 90 kW ... 200 kW (HO)
The pulse frequency can be increased in 2 kHz steps. A higher pulse
frequency reduces the permissible output current.
Possible braking
methods
DC braking, compound braking, dynamic braking with integrated braking
chopper
Degree of protection
IP20
0.37 kW ... 110 kW (HO)
-10 °C … +50 °C (14 °F … 122 °F)
132 kW ... 200 kW (HO)
-10 °C … +40 °C (14 °F … 104 °F)
Operating temperature
(LO) -10 °C … +40 °C (14 °F … 104 °F)
Higher operating
temperatures are possible
when the rated power is
reduced (derating)
Bearing temperature
-40 °C … +70 °C (-40 °F … 158 °F)
Relative humidity
< 95% RH - condensation not permissible
0.37 kW ... 110 kW (HO)
Up to 1000 m (3300 ft) above sea level
Installation altitude
132 kW ... 200 kW (HO)
Up to 2000 m (6500 ft) above sea level
Higher altitudes are
possible when the rated
power is reduced
(derating)
Standards
UL, cUL, CE, C-tick, SEMI F47
In order that the system is UL-compliant, UL-certified fuses, overload
circuit-breakers or intrinsically safe motor protection devices must be
used