5.1
Permissible line supplies
The converter is designed for the following line supplies according to IEC 60364-1 (2005).
● TN system
● TT system
● IT system
General requirements on line supply
The plant builder or machine manufacturer must ensure for operation with rated current I
rated
that the voltage drop between the transformer input terminals and the inverter when operated
with its rated values is less than 4% of the transformer rated current
Restrictions for installation altitudes above 2000 m
Above an installation altitude of 2000 m, the permissible line supplies are restricted.
Restrictions for special ambient conditions (Page 108)
5.1.1
TN line system
A TN line system transfers the PE protective
conductor to the installed plant or system us‐
ing a cable.
Generally, in a TN line system the neutral
point is grounded. There are versions of a TN
system with a grounded line conductor, e.g.
with grounded L1.
A TN line system can transfer the neutral con‐
ductor N and the PE protective conductor ei‐
ther separately or combined.
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH 6HSDUDWHWUDQVIHURI1DQG3(
JURXQGHGQHXWUDOSRLQW
/
/
/
1
3(
Inverter operated on a TN line system
● Inverter with integrated or external line filter:
– Operation on TN line systems with grounded neutral point permissible.
– Operation on TN line systems with grounded line conductor not permissible.
● Inverter without line filter:
– Operation on all TN line systems ≤ 600 V permissible
– Operation on TN line systems > 600 V and grounded neutral point permissible.
– Operation on TN line systems > 600 V and grounded line conductor not permissible.
Connecting-up
5.1 Permissible line supplies
Power Module PM240-2
50
Hardware Installation Manual, 08/2017, A5E33294624B AG
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......