7.5
Technical data, 200 V inverters
Motors for 200 V Power Modules
For the 200 V Power Modules, induction motors are permissible in the range from 25% … 150%
of the inverter power without any restrictions.
Note
Motors for inverter operation
Only use motors that are suitable for operation with inverters with a DC link.
7.5.1
General data, 200 V inverters
Property
Version
Line voltage
FSA … FSC
200 V … 240 V 1-ph. AC ± 10% 0.55 kW … 4 kW - LO
0.37 kW … 3 kW - HO
200 V … 240 V 3-ph. AC ± 10% 0.55 kW … 7.5 kW - LO
0.37 kW … 5.5 kW - HO
FSD … FSF
200 V … 240 V 3-ph. AC ± 10% (in operation -20% < 1 min)
Line supply configurations Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 50)
Line impedance
FSA … FSC
2% ≤ Uk < 4%. For Uk < 2%, we recommend a line reactor, or a Power Module
with the next higher power rating.
FSD … FSF
No restrictions
Power factor λ
FSA … FSC
0.7 without line reactor for Uk ≥ 2%
0.85 with line reactor for Uk < 2%
FSD … FSF
0.95
Output voltage
0 V … 0.95 3-ph. AC × input voltage
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 … 550 Hz, depending on the control mode
Inrush current
< LO base load input current
Overvoltage category ac‐
cording to EN 61800-5-1
III for line supplies
Pulse frequency
4 kHz (factory setting),
Adjustable as follows in 2 kHz steps:
• 2 kHz … 16 kHz for devices with an LO base load output from 0.55 kW … 30 kW.
• 2 kHz … 8 kHz for devices with an LO base load output 37 kW and higher
If you increase the pulse frequency, the inverter reduces the maximum output current.
Short-circuit current rating
(SCCR) and branch protec‐
tion
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC (
support.industry.siemens.com/cs/ww/en/view/109479152
Braking methods
DC braking, compound braking, dynamic braking with integrated braking chopper
Technical data
7.5 Technical data, 200 V inverters
Power Module PM240-2
80
Hardware Installation Manual, 08/2017, A5E33294624B AG
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......