Table 7-33
PM240-2, PT, frame size D, 500 V to 690 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PH24-2UL0
6SL3211-1PH24-2AL0
LO base load power
37 kW
LO base load input current
40 A
LO base load output current
42 A
HO base load power
30 kW
HO base load input current
36 A
HO base load output current
35 A
Fuse according to IEC
Fuse according to UL, class J
33NA3822-6 (63 A)
60 A
Power loss without filter
0.93 kW
1)
Power loss with filter
0.94 kW
1)
Required cooling air flow
55 l/s
Weight without filter
20.5 kg
Weight with filter
22.5 kg
1)
approx. 0.8 kW through the heatsink
Table 7-34
PM240-2, IP20, frame size E, 500 V … 690 V 3 AC
Article No. - without filter
Article No. - with filter
6SL3210-1PH25-2UL0
6SL3210-1PH25-2AL0
6SL3210-1PH26-2UL0
6SL3210-1PH26-2AL0
LO base load power
45 kW
55 kW
LO base load input current
50 A
59 A
LO base load output current
52 A
62 A
HO base load power
37 kW
45 kW
HO base load input current
44 A
54 A
HO base load output current
42 A
52 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3824-6 (80A)
80 A
3NA3824-6 (80A)
80 A
Power loss without filter
1.07 kW
1.30 kW
Power loss with filter
1.08 kW
1.31 kW
Required cooling air flow
83 l/s
83 l/s
Weight without filter
26 kg
26 kg
Weight with filter
28 kg
28 kg
Technical data
7.7 Technical data, 690 V inverters
Power Module PM240-2
104
Hardware Installation Manual, 08/2017, A5E33294624B AG
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......