7.7.3
Current derating depending on the pulse frequency, 690 V inverters
Article number
LO power [kW]
LO base load output current [A]
Pulse frequency [kHz]
2 *)
4
6SL3210-1PH21-4 . L0
11
14
8.4
6SL3210-1PH22-0 . L0
15
19
11.4
6SL3210-1PH22-3 . L0
18.5
23
13.8
6SL3210-1PH22-7 . L0
22
27
16.2
6SL3210-1PH23-5 . L0
30
35
21
6SL321 . -1PH24-2 . L0
37
42
25.2
6SL3210-1PH25-2 . L0
45
52
31.2
6SL321 . -1PH26-2 . L0
55
62
37.2
6SL3210-1PH28-0 . L0
75
80
48
6SL3210-1PH31-0 . L0
90
100
60
6SL3210-1PH31-2 . L0
110
115
69
6SL321 . -1PH31-4 . L0
132
142
85.2
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
Technical data
7.7 Technical data, 690 V inverters
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
107