4.4
Mounting the Power Modules
Take note of the following listed specifications when installing the Power Module.
Protection against the spread of fire
The device may be operated only in closed housings or in control cabinets with protective
covers that are closed, and when all of the protective devices are used. The installation of the
device in a metal control cabinet or the protection with another equivalent measure must
prevent the spread of fire and emissions outside the control cabinet.
Protection against condensation or electrically conductive contamination
Protect the device, e.g. by installing it in a control cabinet with degree of protection IP54
according to IEC 60529 or NEMA 12. Further measures may be necessary for particularly
critical operating conditions.
If condensation or conductive pollution can be excluded at the installation site, a lower degree
of control cabinet protection may be permitted.
Installing
NOTICE
Damage caused by overheating as a result of an inadmissible mounting position
When incorrectly mounted, the Power Module can overheat and therefore be damaged.
● Only install the Power Module in a vertical position with the motor connectors at the bottom.
● Maintain the minimum clearances to other components.
● Use the specified installation parts and components.
● Comply with the specified torques.
Installing/mounting
4.4 Mounting the Power Modules
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
33
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......