Installing/mounting
4.1 Installation conditions
Power Module PM240-2
24
Hardware Installation Manual, 08/2017, A5E33294624B AG
●
Carefully note that for plants and systems in conformance with UL/cUL, the line and
output voltage may not be higher than 600 V.
●
Only use copper cables rated for 60 °C or 75 °C.
●
FSE, IP20: Only use cables that are certified for temperatures of 75 °C to connect the
braking resistor.
●
FSE, PT: Only use cables that are certified for temperatures of 75 °C to connect the line
supply, motor and braking resistor.
●
The inverters are Open Type devices.
●
The push-through FSD ... FSF inverters are Open Type devices. At the rear of the control
cabinet they fulfil Enclosure Type 1.
●
The DC-link terminals, DCP and DCN, were not investigated regarding conformance with
UL/cUL.
Additional requirements for CSA compliance, frame sizes FSA … FSC
Install the inverter with an external suppression device with the following properties:
●
Surge protection device with the appropriate certification (category checking numbers
VZCA and VZCA7)
●
Rated supply voltage
–
240 V (phase with respect to ground), 240 V (phase to phase) for 200 V inverters
–
480 V (phase to phase) for 400 V inverters
●
Terminal voltage, V
PR
–
max. 2000 V for 200 V inverters
–
max. 2500 V for 400 V inverters
●
Overvoltage category III
●
Pollution degree 2
●
Suitable for SPD applications, type 1 or type 2
Alternatively, use a surge protection device, article number 5SD7 424-1 from Siemens AG.
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......