Table 7-24
PM240-2, IP20, Frame Size D, 3-ph. AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3210-1PE27-5UL0
6SL3210-1PE27-5AL0
LO base load power
37 kW
LO base load input current
70 A
LO base load output current
75 A
HO base load power
30 kW
HO base load input current
62 A
HO base load output current
60 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3830 (100 A)
100 A
Power loss without filter
1.09 kW
Power loss with filter
1.10 kW
Required cooling air flow
55 l/s
Weight without filter
17 kg
Weight with filter
18.5 kg
Table 7-25
PM240-2, PT, frame size D, 3 AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3211-1PE27-5UL0
6SL3211-1PE27-5AL0
LO base load power
37 kW
LO base load input current
70 A
LO base load output current
75 A
HO base load power
30 kW
HO base load input current
62 A
HO base load output current
60 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3830 (100 A)
100 A
Power loss without filter
1.09 kW
1)
Power loss with filter
1.10 kW
1)
Required cooling air flow
55 l/s
Weight without filter
20 kg
Weight with filter
21.5 kg
1)
Approx. 1 kW through the heatsink
Technical data
7.6 Technical data, 400 V inverters
Power Module PM240-2
96
Hardware Installation Manual, 08/2017, A5E33294624B AG
Содержание SINAMICS G12
Страница 2: ......
Страница 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 10: ...Changes in this manual Power Module PM240 2 10 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 118: ...Spare parts Power Module PM240 2 118 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 156: ...Appendix A 4 Abbreviations Power Module PM240 2 156 Hardware Installation Manual 08 2017 A5E33294624B AG ...
Страница 159: ......