Wiring the S7-400
4-17
Automation System S7-400 Hardware and Installation
A5E00850741-01
4.11
Wiring Rules
Lines and Tools
For wiring the S7-400 modules, there are some rules for the cables and tools to
use.
Rules for
... Power Supply
... Front Connectors
Crimp terminal
Screw-type
terminal
Spring-type terminal
Conductor
cross-sections:
Outer diameter:
3 to 9 mm
Flexible cond.
without wire end
ferrule
no
0.5 to 1.5 mm
2
0.25 to 2.5 mm
2
0.08 to 2.5 mm
2
Flexible cond. with
wire end ferrule
230 VAC:
flexible
sheathed cable
3 x 1.5 mm
2
24 VDC:
flexible
sheathed cable
3 x 1.5 mm
2
or
individual wires
1.5 mm
2
no
0.25 to 1.5 mm
2
0.25 to 1.5 mm
2
No. of conductors
per terminal
1
1
1
*
1
*
Stripping length of
single conductors
7 mm
5 mm
8 to 10 mm without
ferrule
10 mm with ferrule
8 to 10 mm without
ferrule
10 mm with ferrule
Wire end ferrules
230 VAC:
with
insulating collar to
DIN 46228 E1,5-8
24 VDC
: without
insulating collar to
DIN 46228, shape A,
short version
-
with or without
insulating collar to
DIN 46228 Part 1
or 4, Shape A,
normal version
with or without
insulating collar to
DIN 46228 Part 1 or
4, Shape A, normal
version
Blade width and
shape of the screw
driver
3.5 mm (cylindrical
shape)
-
3.5 mm (cylindrical
shape)
0.5 mm x 3.5 mm
DIN 5264
Tightening torque:
for connecting
conductors
0.6 to 0.8 Nm
-
0.6 to 0.8 Nm
-
*
You can also connect a combination of two conductors of up to 1.0 mm each to a screw-type
or spring-loaded terminal. You must use special wire end ferrules for this purpose. Two types
and manufacturers of such ferrules are given below:
•
Phoenix TWIN
Type no. 32 00 81 0, for 2 x 1 mm
2
•
AMP
Order no. 966 144-4, for 2 x 1 mm
2
Note
You must use shielded cables for the analog modules (see Section A.5).
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...