Wiring the S7-400
4-14
Automation System S7-400 Hardware and Installation
A5E00850741-01
Connecting the Load Voltage Ground
Many output modules require an additional load voltage to switch the actuators.
Two different modes are possible for this load voltage:
•
Non-isolated operation
•
Floating operation
The following table shows how the load voltage ground is connected in the
individual modes.
Table 4-3
Grounded connection load voltage
Mode
Connection of Load Voltage
Non-isolated operation
•
Grounded configuration
•
Ungrounded configuration
to the reference point of the rack; metallic connection
between frame element and chassis ground must be
fitted.
to the reference point of the rack; metallic connection
between frame element and chassis ground must be
fitted.
Floating operation
•
Grounded and ungrounded
configuration
Left open or to any point, but not to protective ground
or reference potential M of operating voltages
The following figure shows how the load voltage ground is connected for
non-isolated operation.
Metallic connection, remove for
ungrounded configuration
Ground terminal for
load voltage
Figure 4-7 Grounded connection load voltage
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...