Assembling and Installing Systems
A-31
Automation System S7-400 Hardware and Installation
A5E00850741-01
Suppression for DC-Operated Coils
DC-operated coils are interconnected to diodes or Zener diodes.
+
-
+
-
With diode
With Zener diode
Figure A-9
Suppression for DC-Operated Coils
Suppression with Diodes / Zener Diodes
Suppression with diodes or Zener diodes exhibits the following characteristics:
•
Switching overvoltages can be avoided entirely. A Zener diode has a higher
turn-off voltage.
•
High turn-off delay (6 to 9 times higher than without suppressor circuits)
The Zener diode switches off more quickly than a diode circuit.
Suppression with AC-Operated Coils
AC-operated coils are suppressed with varistors or RC elements.
With varistor
With RC element
~
~
~
~
Figure A-10 Suppression with AC-Operated Coils
Suppression with a varistor exhibits the following characteristics:
•
The amplitude of the switching overvoltage is limited but not attenuated.
•
The steepness of the surge voltage remains the same.
•
Low turn-off delay.
Suppression with an RC element exhibits the following characteristics:
•
The amplitude and steepness of the switching overvoltage are reduced.
•
Low turn-off delay.
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...