Networking
5-24
Automation System S7-400 Hardware and Installation
A5E00850741-01
PROFIBUS Optical Bus Terminal (OBT)
A PROFIBUS node can be connected to the optical PROFIBUS-DP network via a
PROFIBUS Optical Bus Terminal (OBT) (6GK1 500-3AA00) without an integrated
fiber-optic cable interface (e.g. programming devices (PGs) or operator panels
(OPs), see Figure 5-13).
The programming device/PC is connected to the RS 485 interface of the OBT by
means of the PROFIBUS cable. The OBT is integrated in the optical
PROFIBUS-DP line by means of its fiber-optic cable interface.
5.8.1
Fiber-Optic Cables
Features of the Fiber-Optic Cables
Use Siemens plastic and PCF fiber-optic cables with the following features:
Table 5-4
Features of the Fiber-Optic Cables
Description
SIMATIC NET PROFIBUS
Plastic Fiber-Optic
Duplex Conductor
Plastic Fiber-Optic
Standard Cable
PCF Fiber-Optic
Standard Cable
Standard designation
I-VY2P 980/1000
150A
I-VY4Y2P 980/1000
60A
I-VY2K 200/230
10A17+8B20
Field of application
Indoors with a low
mechanical load,
such as laboratory
test assemblies or in
cabinets:
Cable lengths up to
50 m
Indoor applications:
Cable lengths up to
50 m
Indoor applications:
Cable lengths up to
300 m
Fiber type
Step-index fiber
Core diameter
980
μ
m
200
μ
m
Core material
Polymethyl methacrylate (PMMA)
Quartz glass
Cladding outer diameter
1000
μ
m
230
μ
m
Cladding material
Fluorinated special polymer
Inner sheath
•
Material
•
Color
•
Diameter
PVC
Gray
2.2
0.01 mm
PA
Black and orange
2.2
±
0.01 mm
--
(Without inner sheath)
Outer sheath
•
Material
•
Color
--
PVC
Purple
PVC
Purple
Number of fibers
2
Attenuation at
wavelength
≤
230 dB/km
660 nm
≤
10 dB/km
660 nm
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...