Lengths of Spur Lines
If you do not fit the bus cable directly at the bus connector (for example, when
using a PROFIBUS-DP bus terminal), you must take into account the maximum
possible spur line length.
The following table gives the maximum lengths of spur lines allowed per bus
segment:
Table 5-3
Lengths of Spur Lines per Segment
Transmission Rate Maximum
Length of a
S
Li
Number of Nodes per
Spur Line Length of ...
Maximum
Length of
S
Li
g
Spur Line
1.5 m and
1.6 m
3 m
g
Spur Lines
per Segment
9.6 to 93.75 kbps
3 m
32
32
96 m
187.5 kbps
3 m
32
25
75 m
500 kbps
3 m
20
10
30 m
1.5 Mbps
3 m
6
3
10 m
A spur line is not permissible with transmission rates greater than 1.5 Mbps.
To connect a programming device or PC, use the connecting cable for the
programming with theorder number 6ES7901-4BD00-0XA0. You can use several
connecting cable with this order number for programming devices in one bus
configuration.
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...