Assembling and Installing Systems
A-8
Automation System S7-400 Hardware and Installation
A5E00850741-01
Rule 4: Special EMC Measures
Employ special EMC measures for particular applications (see Section 4.11).
•
Fit suppressors to all inductors which are not controlled by S7-400 modules.
•
Use incandescent bulbs or suppressed fluorescent lamps in the immediate
vicinity of your controller for illuminating cabinets or housings.
Rule 5: Standard Reference Potential
Create a standard reference potential; ground all electrical apparatus if possible
(see Sections 4.10 and 4.12).
•
Install equipotential bonding conductors of sufficient rating when potential
differences exist or are expected between sections of your system.
•
Use specific grounding measures. Grounding the control system is a protective
and functional measure.
•
Connect the system sections and cabinets containing central racks and
expansion racks to the grounding/protective ground system in a star
configuration. This prevents the formation of ground loops.
See also
Cable shielding, page A-13
Cabling outside buildings, page A-19
Cabling inside buildings, page A-17
Mounting of programmable controllers for EMC, page A-9
Содержание Simatic S7-400
Страница 6: ...Preface vi Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 52: ...Installing the S7 400 2 36 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 60: ...Addressing the S7 400 3 8 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 128: ...Networking 5 30 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 148: ...Commissioning 6 20 Automation System S7 400 Hardware and Installation A5E00850741 01 ...
Страница 228: ...Index Index 4 Automation System S7 400 Hardware and Installation A5E00850741 01 ...